Reliability    Safety    Capacity

Solis-(40-60)K-FB

400V: 40K/50K/60K-4G;   480V: 50K-HV/60K-HV

40-60kW three-phase series string inverter are suitable for the installation of three-phase input pv system of commercial and industrial PV plants. WhoseTHDi˂3, low harmonic distortion against grid. Adopt anti-resonance, signle transformer can connect 6M+ in parallel. Perfect commercial site monitoring solution, intelligent redundancy fan.

40-60kW Three Phase Inverter

Leading Features

  • Max. efficiency 99%
  • Intelligent redundant fan-cooling
  • Wide voltage range and low startup voltage
  • Perfect commercial site monitoring solution
  • 4 MPPT input, each rated current is 24A/36A, compatible with high power module
  • THDi<3%, low harmonic distortion against grid
  • Anti-resonance, Supporting over 6MW parallelled in one transformer

Technical Specifications

Input DC

  • Max. input voltage
    1100 V
  • Rated voltage
    600 V
  • Start-up voltage
    200 V
  • MPPT voltage range
    200-1000 V
  • Max. input current
    4*24 A
  • Max. Short Circuit current
    4*37.5 A
  • MPPT number
    4
  • Max. input strings number
    8

Output AC

  • Max. apparent output power
    44 kVA
  • Max. output power
    44 kW
  • Rated grid voltage
    3/N/PE, 220 V / 380 V, 230 V / 400 V
  • Rated grid frequency
    50 Hz / 60 Hz
  • Rated grid output current
    58 A / 60.8 A
  • Max. output current
    66.9 A
  • THDi
    <2%
  • Power Factor
    >0.99 (0.8 leading - 0.8 lagging)

Efficiency

  • EU efficiency
    98.4%

Protection

  • Short circuit protection
    Yes
  • Output over current protection
    Yes
  • Surge protection
    Yes
  • Grid monitoring
    Yes
  • Anti-islanding protection
    Yes
  • Temperature protection
    Yes
  • Strings monitoring
    Yes
  • Anti-PID function
    Optional
  • Integrated DC switch
    Optional

General Data

  • Weight
    75 kg
  • Topology
    Transformerless
  • Self consumption (night)
    <1 W
  • Operating ambient temperature range
    -25~60℃
  • Relative humidity
    0~100%
  • Ingress protection
    Ip65
  • Cooling concept
    Natural convection
  • Max.operation altitude
    4000 m
  • Safety/EMC standard
    IEC/EN 62109-1/-2, IEC/EN 61000-6-2/-4
  • Safty/EMC standard
    G98 or G99, VDE-AR-N 4105 / VDE V 0124, EN 50549-1, VDE 0126 / UTE C 15 / VFR:2019, RD 1699 / RD 244 / UNE 206006 / UNE 206007-1, CEI 0-21, C10/11, NRS 097-2-1,EIFS 2018.2, IEC 62116, IEC 61727, IEC60068, IEC 61683, EN 50530

Features

  • AC connection
    OT Terminal
  • Display
    LCD
  • Communication
    RS485, Optional: Wi-Fi, GPRS
Sales Inquiries:sales@ginlong.com